EasyManua.ls Logo

AUMA SAVEx Series - Terminal Compartment: Close

AUMA SAVEx Series
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Information
For loop topology, automatic termination is performed as soon as the AUMATIC
is connected to the power supply.
In case of a power outage of the AUMATIC, the two RS-485 loop segments will
be automatically connected so that the actuators following these segments re-
main available.
When using a SIMA master station, a redundant loop topology may be estab-
lished.
Connect fieldbus cables:
1. Connect fieldbus cables.
2. If the actuator is the final device in the fieldbus segment (line topology only):
2.1 Connect termination resistor for channel 1 through linking the terminals
31 - 33 and 32 - 34 (standard)
2.2 For AUMA redundancy I or II: Connect termination resistor for channel 2
through linking the terminals 35 - 37 and 36 - 38.
5.3.4. Terminal compartment: close
Figure 32: Close terminal compartment
[1] Cover (illustration shows type of protection Ex e)
[2] Screws for cover
[3] O-ring
[4] Blanking plugs
[5] Cable gland (example)
[6] Connection frame
1. Clean sealing faces of cover [1] and connection frame [6].
2. For Ex plug/socket connector designed as KES flameproof: Preserve joint sur-
faces with an acid-free corrosion protection agent.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease to the O-ring and insert it correctly.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
36
SAVEx 07.2 SAVEx 16.2 / SARVEx 07.2 SARVEx 16.2 Control unit: electronic (MWG)
Electrical connection ACVExC 01.2 Non-Intrusive Modbus RTU

Table of Contents

Related product manuals