58
JGSTATW Instruction Manual
Installation - Device Parameters
DX FUNCTION SYSTEM DEFINITION DEFAULT
SETTING
D01 Heating 0 Pulse Width Modulation
Control 1 On-Off 0.5ºC +/- 0.25ºC 0
2 On-Off 1.0ºC +/- 0.5ºC
D02 Room
-3.0 to
Temperature Offset from
Temperature
3.0ºC
Measured Temperature to 0ºC
Offset Compensate for any error
D03 Sensor probe or
0 Sensor/Cyl stat not Connected
Cylinder thermostat
1 Sensor/Cyl stat Connected
0
connection
D04 Sensor probe 0 D03 must be set to 1 then
used as air sensor external sensor be used as
or floor sensor Air sensor. There will be no
internal temp measurement
0
1 D03 must be set to 1 then external
sensor used for floor protection.
Internal temp is measured by stat
D05 Cooling Control 1 On-Off 0.5ºC +/- 0.25ºC
2
2 On-Off 1.0ºC +/- 0.5ºC
D06 Actuator type 0 NO Normally Open
1
1 NC Normally Closed
D07 Valve protection 0 Disable
1
1 Enable