4007ES Operator’s Manual
Table 6: Report Menu Screen Buttons
Button Description
TrueAlarm Service
Tap the TrueAlarm Service button to generate a report which contains the following information:
• Device Number
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value
• Current Value
• Percent of Alarm: Shows the current value for the sensor. Value is shown as a percentage of 100% (alarm). For
example, if the value shown is 9%, it means that the sensor is currently at 9% of the value required to trigger an
alarm.
• Peak Value: Shows the highest value that the sensor has reached. Value is shown as a percentage of 100% (alarm).
For example, if the value shown is 9%, it means that the peak value experienced by the sensor was 9% of the value
required to trigger an alarm.
• Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty, and Almost Dirty.
TrueAlert NAC Test
Tap the TrueAlert NAC Test button to generate a report which contains the following information for each TrueAlert
device:
• Point ID
• Custom Label
• Device Type
• Candela
TrueAlert Status
The TrueAlert Status Report can be created after the TrueNAC Voltage Drop Test is run.
Tap theTrueAlert Status button to access the Print TAlert Status screen. The All button can be used to generate the
report containing the status for all devices. The Last button can be used to generate a report containing the status of
the last test. The report contains the following information:
• Point ID
• Custom Label
• Pass/Fail
TrueAlarm CO
Tap the TrueAlarm CO button to generate a report with the following information regarding the TrueAlarm CO devices:
• Device Number (on the network)
• Custom Label (custom description of the device)
• Current Device Value (PPM)
• End-of-Life Date
• Device Status (Normal, Trouble)
Active List
Tap the Active List button to access the Print Active List screen, where the Install Mode button can be used to
generate a report containing the following Install Mode list information:
• Point ID
• Custom Label
• Device Status
Verification Tally
Tap the Verification Tally button to generate a report containing the following information for each device supporting
the alarm verification:
• Device Number
• Custom Label
• Device Type
• Point Type
• Tally Count
TrueAlert Self-Test
Tap the TrueAlert Self-Test button to access the Print TA Self-Test screen to generate a report containing the Self-Test
results for the TrueAlert appliances. Tap the ALL button to generate a report with the results for all appliances. Tap the
LAST button to generate a report with result for the last device