Error Message Description
12 Channel 2 Movement Error Servomotor moves when not expected and vice versa
Check wiring and voltages on terminals and 70 – 77
Check servomotors drive in correct direction and damper is not stuck
13 Channel 3 Movement Error Servomotor moves when not expected and vice versa
Check wiring and voltages on terminals and 70 – 77
Check servomotors drive in correct direction and valve is not stack
14 Channel 4 Movement Error Servomotor moves when not expected and vice versa
Check wiring and voltages on terminals and 70 – 77
Check servomotors drive in correct direction and valve is not stuck
15 Channel 7 Movement Error Servomotor moves when not expected and vice versa
Check wiring and voltages on terminals DCI and DCD
Check servomotor drives in correct direction and damper is not stuck
16 Analogue Power Supply Error ADC measured 12V supply out of range
Check wiring for shorts on terminals 41, 47 and 39
17 Digital Power Supply Error ADC measured 3.3V supply out of range
Check for noise on the mains input, wiring and voltages on all terminals
18 EEPROM Error Fault communicating with the on board EEPROM
Contact Autoflame approved local tech centre
19 ADC Error Internal fault
Contact Autoflame approved local tech centre
20 Watchdog Timeout Internal fault
Contact Autoflame approved local tech centre
21 Processor Clock Error Internal fault
Contact Autoflame approved local tech centre
22 System Error Internal fault
Contact Autoflame approved local tech centre
23 Flash Data Error Internal fault
Re-install software SD card
24 Processor Temperature Error Internal fault
Check ambient temperature of unit does not exceed maximum recommended temperature
25 Burner Control Comms Error Internal fault
Contact Autoflame approved local Tech Centre
26 Burner Control Reset Internal fault
Contact Autoflame approved local Tech Centre
27 Software Error Internal fault
Contact Autoflame approved local Tech Centre
28 Zero-Crossing Detection Error Internal fault
Check mains supply going to unit is within acceptable voltage range
29 Mains Input Detection Error Mains input stuck on
Check wiring and voltages on terminals 89 – 92
30 Channel 5 VSD Error Feedback incorrect
Check VSD feedback against commissioned VSD and ensure the feedback is stable
31 Channel 6 VSD Error Feedback incorrect
Check VSD feedback against commissioned VSD and ensure the feedback is stable
Page 41 Mk8 MM End User Guide 22.05.2017