Error Message Description
49 Expansion Servo Hardware Fault Internal fault
Contact Autoflame approved local tech centre
50 Triac Power Supply Error (Check
F2)
Internal fault
Check wiring on terminal 69
Check fuse 2 (2A T)
51 Fused 12V Supply Error (Check
F4)
Internal fault
Check gas/air pressure sensor wiring on terminals 31 – 34, and load detector on 37 – 39
Check fuse 4 (500mA)
52 Fused 13.5V Supply Error
(Check F3)
Internal fault
Check IR scanner wiring on terminals 29, 30, 48, 49 and oil pressure sensor on 48, 49
Check fuse 3 (500mA)
53 Air Pressure Zeroing Fault Commissioned air zero pressure is more than 5mbar from
sensor’s zero value
Check air pressure sensor value during VPS
54 Software error Internal fault
Contact Autoflame approved local Tech Centre
55 Software error Internal fault
Contact Autoflame approved local Tech Centre
56 Software error Internal fault
Contact Autoflame approved local Tech Centre
57 Software error Internal fault
Contact Autoflame approved local Tech Centre
58 Software error Internal fault
Contact Autoflame approved local Tech Centre
59 Software error Internal fault
Contact Autoflame approved local Tech Centre
60 Software error Internal fault
Contact Autoflame approved local Tech Centre
61 Software error Internal fault
Contact Autoflame approved local Tech Centre
62 Software error Internal fault
Contact Autoflame approved local Tech Centre
63 Software error Internal fault
Contact Autoflame approved local Tech Centre
64 ADC Reference Voltage Error Hardware fault
Contac Contact Autoflame approved local Tech Centre
Contact Autoflame approved local Tech Centre
65 Software error Internal fault
Contact Autoflame approved local Tech Centre
66 Software error Internal fault
Contact Autoflame approved local Tech Centre
67 Software error Internal fault
Contact Autoflame approved local Tech Centre
Page 43 Mk8 MM End User Guide 22.05.2017