Lockout Message Description
15 NO CPI Reset Proof of closure switch not made after valves closed
Check wiring on terminal 55 and check proof of closure switches
16 Prolonged Lockout Reset Prolonged voltage detected on terminal 56/ lockout reset
button permanently pressed
Check lockout reset button is not pressed
Check wiring on terminal 56
17 Gas Pressure Low Gas pressure low limit exceeded while firing(gas sensor)
Check gas pressure
Check option/ parameter 136
18 Gas Pressure High Gas pressure high limit exceeded while firing (gas sensor)
Check gas pressure
Check option/ parameter 137
19 RAM Test Failed Hardware fault
Contact Autoflame approved local tech centre
20 PROM Test Failed Hardware fault
Contact Autoflame approved local tech centre
21 FSR Test 1A Internal relay test failed
Check wiring and voltages on terminals 50 – 63
22 FSR Test 2A Internal relay test failed
Check wiring and voltages on terminals 50 – 63
23 FSR Test 1B Internal relay test failed
Check wiring and voltages on terminals 50 – 63
24 FSR Test 2B Internal relay test failed
Check wiring and voltages on terminals 50 – 63
25 Watchdog Fail 2A Internal check failed
Contact Autoflame approved local tech centre
26 Watchdog Fail 2B Internal check failed
Contact Autoflame approved local tech centre
27 Watchdog Fail 2C Internal check failed
Contact Autoflame approved local tech centre
28 Watchdog Fail 2D Internal check failed
Contact Autoflame
29 Input Fault Power supply fault
Check mains voltage to the MM
32 Gas Pressure Low Limit Gas pressure lower than commissioned VPS value
Check gas pressure sensor value
Check option/parameter 136
33 VPS Air Zeroing Gas pressure sensor cannot be zeroed at VPS venting
Check gas pressure is within zero range (see MM Application Possibilities)
Check vent valve
36 Oil Pressure Too Low Oil pressure below offset lower limit during running
Check option/parameter 139
Check oil pressure sensor
37 Oil Pressure Too High Oil pressure above offset upper limit during running
Check option/parameter 140
Check oil pressure sensor
Page 45 Mk8 MM End User Guide 22.05.2017
4 Errors and Lockouts