Lockout Message Description
39 Freeze Timeout MM kept in Phase Hold for more than 10minutes
MM kept in Phase Hold during commissioning for more than 10 minutes
40 Purge Air Pressure Low Insufficient air pressure during purge
Check option/parameter 141
Check air pressure sensor/ air pressure switch
42 Terminal 86 Inverse Input detected on both terminals 85,86 where there
should not be, and vice versa
Check option/parameter 122
Check wiring and voltages on terminals 85, 86
43 Terminal 85/86 Fault Hardware fault on terminals 85/86
Check wiring and voltages on terminals 85, 86 and contact Autoflame
44 Proving Circuit Fail T52 Loss of input on terminal 52; MM must see input at all
times from position to purge to post purge
Check wiring on terminal 52
45 No Proving Circuit Set Secondary proving timeout elapsed
Check option/parameter 157
Check wiring on terminal 52
46 Proving Interlock Timeout Purge interlock timeout elapsed
Check option/ parameters 155 and 158
Check wiring on terminal 81
52 High IR Ambient Flame detected when there should not be
Visually check flame and check IR scanner
Call a certified Commissioning Engineer to investigate
53 IR Comms Lost Loss of comms with IR scanner
Check wiring and screen on terminals 29, 30, 48 and 49
Check that the IR scanner is not removed from the magnetic ring socket
54 Watchdog Long X A Internal check failed
Contact Autoflame approved local tech centre
55 Watchdog Long Y A Internal check failed
Contact Autoflame approved local tech centre
56 Watchdog Off A Internal check failed
Contact Autoflame approved local tech centre
57 Watchdog Short X B Internal check failed
Contact Autoflame approved local tech centre
58 Watchdog Short Y B Internal check failed
Contact Autoflame approved local tech centre
59 Watchdog Long X B Internal check failed
Contact Autoflame approved local tech centre
60 Watchdog Long Y B Internal check failed
Contact Autoflame approved local tech centre
61 Watchdog Off B Internal check failed
Contact Autoflame approved local tech centre
62 UV Signal Too High Internal check failed for UV
Check wiring on terminals 21, 22, 50 and 51
22.05.2017 Mk8 MM End User Guide Page 46
4 Errors and Lockouts