Lockout Message Description
63 Purge Limit Switch Interlock not made on terminal 81
Check option/ parameter 155
Check wiring on terminal 81
64 Start Limit Switch Interlock not made on terminal 80
Check option/ parameter 154
Check wiring on terminal 80
65 FSR A Internal check failed
Check wiring and voltages on terminals 50 – 63
66 FSR B Internal check failed
Check wiring and voltages on terminals 50 – 63
67 Gas Sensor Comms Signal lost from gas pressure sensor
Check wiring and screen on terminals 31 – 34
68 Gas Sensor Type Internal fault
Contact Autoflame approved local tech centre
69 Gas Sensor Fault Internal pressure sensor fault
Contact Autoflame approved local tech centre
70 UV Pot Fault Internal UV scanner fault
Contact Autoflame approved local tech centre
71 Air Sensor Comms Signal lost from air pressure sensor
Check wiring and screen on terminals 31 – 34
72 Air Sensor Type Internal fault
Contact Autoflame approved local tech centre
73 Air Sensor Fault Internal pressure sensor fault
Contact Autoflame approved local tech centre
74 Air Sensor Zero Air pressure is more than 5mbar from sensor’s zero value
Check air pressure sensor value during VPS
75 Air Sensor Signal High Air pressure is above 400mbar
Check Autoflame approved local tech centre
76 Air Sensor Error Window Air pressure outside of these limits for 3 seconds
Check air pressure
Check option/parameter 147
77 Wait Air Switch Timeout Voltage has not been reset for 2minutes
Check air pressure sensor value during VPS
Check voltage has been reset on terminal 54 within 2minutes before run to purge
Check wiring and voltage on terminal 54
78 Gas Proving Fail High Gas pressure too high during VPS
Isolate gas
Check 1
st
main valve and vent valve
Check option/ parameters 133 and 134
Call a certified Commissioning Engineer to investigate
79 FSR Test 1C Hardware fault
Contact Autoflame approved local tech centre
80 Timeout on Reaching Purge Time set in option/parameter 124 has elapsed
Check option/parameter 124
81 Oil Pressure Sensor Fault No comms received from oil pressure sensor
Check wiring and screen on terminals 48, 49
Page 47 Mk8 MM End User Guide 22.05.2017