GS1 Series AC Drive User Manual
4–5
Chapter 4: AC Drive Parameters
Protection
GS1
Parameter
Description Range Default
6-00
Electronic Thermal Overload
Relay
0: Constant Torque
1: Variable Torque
2: Inactive
0
6-01
Auto Restart after Fault 0 to 10 0
6-02
Momentary Power Loss
0: Stop operation after momentary
power loss
1: Continue operation after momentary
power loss, speed search from Speed
Reference
2: Continue operation after momentary
power loss, speed search from
Minimum Speed
0
6-03
Reverse Operation Inhibit
0: Enable Reverse Operation
1: Disable Reverse Operation
0
6-04
Auto Voltage Regulation
0: AVR enabled
1: AVR disabled
2: AVR disabled during decel
3: AVR disabled during stop
0
6-05
Over-Voltage Trip Prevention
0: Enable Over-voltage Trip Prevention
1: Disable Over-voltage Trip Prevention
0
6-06
Auto Adjustable Accel/Decel
0: Linear Accel/Decel
1: Auto Accel, Linear Decel
2: Linear Accel, Auto Decel
3: Auto Accel/Decel
4: Auto Accel/Decel Stall Prevention (limited
by 1-01, 1-02, 1-05 and 1-06)
0
6-07
Over-Torque Detection Mode
0: Disabled
1: Enabled during constant speed operation
2: Enabled during acceleration
0
6-08
Over-Torque Detection Level 30 to 200% 150
6-09
Over-Torque Detection Time 0.1 to 10.0 0.1
6-10
Over-Current Stall Prevention
during Acceleration
20 to 200% 150
6-11
Over-Current Stall Prevention
during Operation
20 to 200% 150
6-12
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec 2.0
6-13
Base-Block Time for Speed Search 0.3 to 5.0 sec 0.5
6-14
Maximum Speed
Search Current Level
30 to 200% 150
6-15
Upper Bound of
Output Frequency
0.1 to 400.0Hz 400.0
6-16
Lower Bound of
Output Frequency
0.0 to 400.0Hz 0.0
Parameter can be set during RUN Mode.