Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 94
14.3.2.5 Manual Test ON - Other Outputs
This chapter describes how to test other outputs (outputs to Fire
Protection Equipment). The test requires Access Level 3 (password
restricted).
When the test is initiated, a test signal will be sent to the selected Fire
Protection Equipment.
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
3
To select TEST, press 1.
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
3 OUTPUT CONTROL
19:23
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
3 OUTPUT CONTROL
19:23
NOTE:
Before this test is performed
, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected
. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is to
be tested.