AUX Air Conditioner Service manual
8
ASW-12A+12A2/EA(L)2-III
Model No
Items
Indoor Unit A
(System A)
Indoor Unit B
(System B)
Outdoor Unit
Type Wall mounted model Heating pump
Cooling kw 3.2 3.2 /
Dehumidify kg/h 1.1 1.1 /
Heating kw / / /
Noise level dB(A) 41 41 62
Cooling 2.56 2.56 /
Performance
EER
Heating
W/W
2.56 2.56 /
Power supply φ-V-Hz 1 / 208-230V~/ 60Hz
Cooling 1250 1250 2500
Rated input
Heating
W
/ / /
Cooling 5.7 5.7 11.4
Rated current
Heating
A
/ / /
Length m 2 2 4.8
Supply cord
Class / 250V 10A 250V 10A 400V 25A
Starting Current A 30.5 30.5 /
Electrical Data
Fuse capacity A 3.15 3.15 3.15
Refrigerant/Charge g R22/1280 R22/1280 /
Type / Rotary Rotary /
Model / 2P20S236A1G 2P20S236A1G /
Rated input W 1235 1235 /
Compressor
Overload
Protector
/ Outer Outer /
Heat exchanger Row*Hole 2*13 2*13 2*31
Type Capillary tube
Refrigerating System
Expansion device
Specification(mm) φ3.0*1000 φ3.0*1000
/
Air Volume m3/h 520 520 /
Cooling r/min 1180/1050/900/800 1180/1050/900/800 860 Fan Speed
H/M/L/Q
Heating r/min / / /
Fan type / Cross flow Cross flow Propeller fan
Fan System
Fan motor output W 19 19 68
Connecting
Pipe
Gas /Liquid OD(mm)*L(mm)
Φ9.52×5000/Φ6.35×5000
Connection
Drainage Pipe OD(mm)*L(mm)
Φ14×780
Suitable area m2 12-21 12-21 /
Net dimensions
(W x H x D)
mm 745*250*210 745*250*210 331*846*901
Others
Net weight kg 10.5 10.5 75