CANDPSX user manual rev 2 Page 11 of 42
____________________ _
3.4.4 Profibus-DP Watch-dog indication disable
To disable the Profibus-DP watch-dog indication, in CANopen Master and CANopen Slave
modality, set the parameter 2024h:
Property
Value
Parameter
2024h
Logic View menu
All parameters/System/Profibus-DP
Data type
8 bit unsigned int
Value
0 = enable wath-dog Profibus-DP indication
1 = disable wath-dog Profibus-DP indication
Default value
0
Access
Read/Write
3.4.5 Baud rate autodetection
The baud rate is set by the Profibus-DP Master and can be monitored by reading the parameter
2030h:
Property
Value
Parameter
2030h
Logic View menu
All parameters/System/Profibus-DP
Data type
32 bit int
Measurement unit
bit/s
Value
3FFFFFFFh = autodetection running
12000000, 6000000, 3000000, 1500000, 500000,
187500, 93750, 19200, 9600
Access
Read-only
3.4.6 Status of the Profibus-DP dual port
To monitor the status of the Profibus-DP dual port, read the parameter 2031h:
Property
Value
Parameter
2031h
Menu selection Logic View
All parameters/System/Profibus-DP
Data type
32 bit int
Measurement unit
--
Value
0 = awaiting parameters assignment
1 = awaiting configuration
2 = data exchange
3 = error
Access
Read-only
The data-exchange status is also reported by the DEA-PB yellow led (see § 40).