User Manual
Ultra-compact, universal
VLF High Voltage Testing Set with Tan Delta
Firmware V2
ENGLISH
DHV0086 Rev06
b2 electronic GmbH
Riedstrasse 1
6833 Klaus
Austria
T +43 (0) 5523 57373
F + 43 (0) 5523 57373-5
www.b2hv.at
info@b2hv.at
Subject to alterations.
Errors excepted.
Illustrations are not binding.
ZERTIFIZIERT
TÜV AUSTRIA CERT GMBH
EN ISO 9001
ZERTIFIKAT NR. 20 100 92003758
Question and Answer IconNeed help?

Do you have a question about the B2 HVA28 and is the answer not in the manual?

Summary

Safety

General, Work, and Personnel Safety

Covers essential safety guidelines, hazards, and personnel requirements.

Appropriate Applications and Operator Qualifications

Lists suitable test applications and defines mandatory operator qualifications.

Design and Construction

Instrument Setup Procedures

Guides through initial setup, including date, time, reporting, units, system info, language, and region.

Test Procedure

Equipment Setup and Connection Diagrams

Covers setup steps and connection diagrams for various tests.

Step-by-Step Equipment Setup Guide

Details all steps for connecting cables, power, interlocks, and system startup.

5.2 Manual Test Mode Operations

Guides on performing tests and setting report details in Manual Test Mode.

5.2.2 Manual Test Parameters Setup

Guides on setting waveform, frequency, arc management, and DUT setup.

5.2.3 Running a Manual Test

Step-by-step guide on how to execute a manual test.

5.3 Automatic Test Mode Overview

Introduces Automatic Test Mode for satisfying specific requirements.

5.4 Interrupting a Test Methods

Explains methods for interrupting a test: routine, alternative, and emergency stop.

Tan Delta

Disconnection Procedure

Normal Disconnection Procedure Steps

Details steps for safely disconnecting the HVA, including emergency stop and discharge.

System Failure Disconnection Procedure

Describes disconnection steps in case of system failure, using a discharge stick.

Instrument Care

B2 HVA28 Specifications

General IconGeneral
Voltage Range0 - 28 kVrms
Current Range0 - 50 mArms
Frequency Range0.01 Hz - 0.1 Hz
WaveformSinusoidal
ModelB2 HVA28
Output Voltage0 - 28 kVrms
Load Capacity1.0 µF @ 0.1 Hz @ 28 kV
Testing CapabilitiesWithstand testing, cable diagnostics (Tan Delta, Partial Discharge)
AccuracyVoltage: ±1% ±3 digits, Current: ±1% ±3 digits, Tan Delta: ±1 x 10⁻⁴
DisplayIntegrated computer with 12.1" touch screen
Power Supply90 - 264 V, 47 - 63 Hz, 1.2 kVA
Dimensions550 x 450 x 330 mm (21.7 x 17.7 x 13.0 in)
Weight36 kg (79 lbs)