MZ-RD – Multi-Zone Remote Display
32 Instruction 3015-5157
4.9. The Calibration Screen
NOTE: Calibration cannot be performed on the remote device. Information for
performing this procedure on the main monitor is provided below.
4.9.1. Overview
The Calibration Screen is used to adjust the calibration factor for each refrigerant gas. It is also
used to program the instrument for new gasses.
IMPORTANT: Changing information on CAL FACTORS will VOID the factory
calibration. Typically, the unit will remain within the factory-calibrated accuracy
indefinitely and no calibration is required. Complex software algorithms adjust for
temperature drift, IR source aging, and pressure changes in order to keep the unit
within factory accuracy specifications.
4.9.2. Navigating to the Calibration Screen
On the System Screen, select the target gas monitor and access that monitor’s Setup Screen
#1. Then select the CAL option to go to the selected monitor’s Calibration Screen.