EasyManua.ls Logo

Bailey IMCIS12 - Page 49

Bailey IMCIS12
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TERMINATION UNIT (NTCS04) CONFIGURATION
INTRODUCTION
WBPEEUI240755B0 A - 3
Table A-3. Analog Output Dipshunt Configuration
Application/Signal Type Dipshunt Configuration XU9
Both outputs in voltage mode
Output 1 in voltage mode, output 2 in
current mode
Output 1 in current mode, output 2 in
voltage mode
Both outputs in current mode (no dip-
shunt required)
Table A-4. Digital Input Dipshunt Configuration
Application/Signal Type Dipshunt Configuration XU5-XU7
System powered E3/E4
Field powered
1
NOTE:
1. Using the field device to complete the path to ground is commonly referred to as
switching neu-
tral
. Using the field device to complete the path to the I/O module is referred to as
switching hot
.
If switching hot is the desired method, the field powered dipshunt configuration must be used. If
system power is required, it should be wired as a field source. Refer to Figure A-2 for an example
of switching hot and switching neutral.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
TP27118A
1 2 3 4 5 6 7 8

Table of Contents

Related product manuals