7.EtherNet/IP Connection Procedure
7.5.2. Checking Sent and Received Data
Check that correct data is sent and received.
In this procedure, the output of the Network Module is performed, which may
have a risk of unexpected operation of the devices connected to the Network
Module.
Ensure safety before you proceed with this operation check described here.
If you cannot ensure safety, do not proceed. When you perform this operation
check, make sure to complete all the steps and make the output of the Network
If you wire the I/O in the state where the devices are powered ON, this may
cause damage to the devices.
Always read and follow the information provided in all safety precautions in the
manuals for each device to be wired.
If you change the variable values on a Watch Tab Page when Sysmac Studio is
online with the CPU Unit, the devices connected to the Controller may operate
regardless of the operating mode of the CPU Unit.
Always ensure safety before you change the variable values on a Watch Tab
Page when Sysmac Studio is online with the CPU Unit.
1
Select Watch Tab Page from the
View Menu in Sysmac Studio.
Select the Watch1 Tab.