B&C Electronics CL 7685
Operator’s Manual - Rev. C - 05/05
- 28 –
[MODE] to stop the procedure and to go back to D3/D4
5A. [/\] [\/] to insert the hysteresis value
6A. [ENT] to confirm and to go to the delay time selection
_
|CAL SA D: 10.0s | Delay time calibration
D 10.0 s: actual delay time value
[MODE] to stop the procedure and to go back to D3/D4
7A. [/\] [\/] to insert the delay time value
8A. [ENT] to confirm and to go back to D3/D4
MESSAGE FUNCTION
_
| UPDATE
| all the date has been memorized
PFM function
The instrument will show the following display:
_
|CAL SA BP: 0.10 |
BP 0.10: actual proportional band value
[MODE] to stop the procedure and to go back to D3/D4
5B. [/\] [\/] to select the proportional band value
6B. [ENT] to confirm and to go to the selection of the maximum pulse frequency
value
_
|CAL SA F:100 i/m|
F:100 i/m: actual pulse frequency value
[MODE] to stop the procedure and to go back to D3/D4
7B. [/\] [\/] to select the frequency value
8B. [ENT] to confirm and to go back to D3/D4