7.14 ANALOG OUTPUT N°2 RANGE
_ _
|CAL OUT2: 0/20mA| |CAL OUT2: 4/20mA|
0/20mA (4/20mA): range selected
Active keys: [MODE] - [/\] [\/] - [ENT]
_
|CAL P1: 0.000 ppm|
P1: begin of range
0.000 PPM: measuring value related to 0/4 mA
Active keys: [MODE] - [/\] [\/] - [ENT]
_
|CAL P2: 2.000 ppm|
P2: end of range
2.000 PPM: measuring value related to 20 mA
Active keys: [MODE] - [/\] [\/] - [ENT]
IMPORTANT NOTE 1: if the value related to P1 is higher than the value related to P2 the analog
output will be the "reverse", otherwise will be the "direct" type.
7.15 SET-POINT A OPERATING MODE
_
|SET A ACT:On/Off| (PWM-PFM)
On/Off, PWM, PFM: set-point A operating mode
Active keys: [MODE] - [/\] [\/] - [ENT]
7.16 SET-POINT A FUNCTION
_ _
|SET A F. : LO | |SET A F. : HI |
LO: minimum (relay activated for meas. below set-point)
HI: maximum (relay activated for meas. above set-point)
Active keys: [MODE] - [/\] [\/] - [ENT]