3. Create a Read Rule to read the four universal inputs from the I/O board (Modbus slave 200) and write the values in
local registers 1 through 4.
4. Create a Write Rule to write the four local register values to the DXM display registers 1102 through 1105 (Modbus
Slave 201). Define the Write Rule to only write the display registers when the inputs change.
5. Save the XML configuration from the File > Save As
menu.
6. Connect to the DXM Controller using a USB cable and select Device > Connection Settings from the menu bar.
7. Upload the XML configuration file to the DXM Controller by selecting Device > Upload Configuration to Device
from the menu bar.
After a configuration file is uploaded, the DXM Controller reboots. The new configuration is now running.
Turning on any one of the universal inputs 1 through 4 on the I/O base board of the DXM Controller now turns on an LED
on the display.
On the DXM Controller's LCD menu, the arrow on the left side of the register line indicates this local register can be written
to. Try changing the configuration to delete the Read Rule then turn on/off the LEDs by changing the register value
through the LCD display.