Threshold
ON point
Time
Input Value
Input
Hysteresis
OFF point
In the example shown graphically, the input is considered on at 15 mA.
To consider the input off at 13 mA, set the hysteresis to 2 mA. The input
will be considered off when the value is 2 mA less than the threshold.
Input Type. Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input Type
Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature °C/°F.
Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent
temperature units in degrees Celsius.
Universal Input Register Ranges
Register Types Unit Minimum Value Maximum Value
Discrete input/output 0 1
Universal input 0 to 10 V mV 0 10000
6
Universal input 0 to 20 mA µA 0 20000
6
Universal input temperature (–40 °C to +85 °C) C or F, signed, in tenths of a
degree
–400 850
Universal potentiometer unsigned 0 65535
Analog Output Parameter Modbus Registers
Modbus Register Analog Output Description
4008 Analog Output 1 0 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
After changing the jumper position, write the appropriate value to the Modbus
registers to define your analog output to match the setting selected by the jumper.
2 = 0 to 20 mA output (default)
3 = 0 to 10 V output
4028 Analog Output 2
6
Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
DXM100 Controller Instruction Manual