Manual 2100-597G
Page 6 of 68
TABLE 1A
Factory Built-In Electric Heat Table
VENTILATION OPTIONS
B – Blank-Off Plate
M – Multi-Speed CRV
N – Multi-Speed CRV with
Economizer Mode
Q – Modulating CRV (0-10Vdc)
R – ERV
I-TEC Series General Information
I-TEC MODEL NOMENCLATURE
I 36 A 1 D A 0Z R P 4 X X 2
SPECIAL UNITS
D – Dehum.
REVISION
VOLTS & PHASE
A – 230/208, 60-1
B – 230/208, 60-3
C – 460-60-3
COIL TREATMENT
X – Std. Hydrophilic Fin Evap. &
Uncoated Alum. Cond. Coil
1 – Phenolic Coated ID Coil
2 – Phenolic Coated OD Coil
3 – Phenolic Coated ID & OD Coil
CONTROLS
X – 24V Terminal Block Only w/o
CompleteStat
TM
1 – CompleteStat
TM
THO (Temp,
Humidity & Occupancy)
2
– CompleteStat
TM
THO w/CO
2
3 – CompleteStat
TM
THO w/Ethernet
4
– CompleteStat
TM
THO w/CO
2
&
Ethernet
MODEL
SERIES
NOMINAL
CAPACITY
30 – 30,000 BTUH
36 – 36,000
42 – 42,000
48 – 48,000
60 – 60,000
ELECTRIC HEAT
0Z – No heat w/breaker
04 – 4KW 1-Phase
05 – 5KW 1-Phase
06 – 6KW 3-Phase
09 – 9KW 3-Phase
10 – 10KW 1-Phase
15 – 15KW 1 & 3-Phase
18 – 18KW 3-Phase
20 – 20KW 1-Phase
FILTER OPTIONS
P – 2" Pleated MERV 8
M – 2" Pleated MERV 11
N – 2" Pleated MERV 13
COLOR OPTIONS
X – Beige paint
1 – White paint
4 – Gray paint
SYSTEM TYPE:
AIR CONDITIONING
RESERVED
Note: CompleteStat
TM
must be
field installed & wired. All units
have 24V terminal block.
Motor will deliver consistent CFM through voltage supply range with no deterioration.
Continuous fan CFM is the total air being circulated during continuous fan mode.
Will occur automatically with a call for "W3" or "Emergency Heat" signal from the thermostat.
TABLE 1B
Indoor Blower Performance
Models I30A1DA I30A1DB I30A1DC
I36A1DA
I42A1DA
I36A1DB
I42A1DB
I36A1DC
I42A1DC
I48A1DA
I48A1DB
I60A1DB
I48A1DC
I60A1DC
I60A1DA
KW
240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1
BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH
4.0
13,652 10,239
5.0
17,065 12,799 17,065 12,799 17,065 12,799 17,065 12,799
6.0
20,478 15,359 20,478 20,478 15,359 20,478 20,478 15,359 20,478
9.0
30,717 23,038 30,717 30,717 23,038 30,717 30,717 23,038 30,717
10.0
34,130 25,598 34,130 25,598 34,130 25,598 34,130 25,598
15.0
51,195 38,396 51,195 38,396 51,195 51,195 38,396 51,195 38,396 51,195 51,195 38,396
18.0
61,434 46,076 61,434
20.0
68,260 51,195 68,260 51,195
MODEL
Rated
ESP
MAX
ESP
Continuous
Airflow
Rated 2nd
Stage CFM
Rated 1st
Stage CFM
5 - 9KW
CFM
m
13.5 - 18KW
CFM
I30A1D .15 0.50 500 900 650 700 1400
I36A1D .15 0.50 600 1150 850 700 1400
I42A1D .20 0.50 650 1300 950 700 1400
I48A1D .20 0.50 725 1500 1050 700 1400
I60A1D .20 0.50 850 1700 1200 700 1400