9492600990 19-11
DECS-150 BESTlogicâ„¢Plus
Name
Description
Symbol
Active Power Level
Select
This element allows selection of the active
power level.
When an input is true, the corresponding
active power level is selected.
When no inputs are true, the active power
level is 0.0.
When multiple inputs are true, the highest
active power level is selected. For example, if
inputs 2 and 3 are true, active power level 3 is
selected.
Alarm Reset
When true, this element resets all active
alarms.
APC Bridge Disable
When true, this element disables APC Bridge
mode.
APC Disable
When true, this element disables Grid Code
APC mode.
Auto Enable
When true, this element sets the unit in Auto
mode (AVR).
Auto Transfer Enable
When true, this element sets the unit as
secondary. When false, the unit is primary.
Configurable Element
1-8
Configurable elements are connected to the
logic scheme as outputs. These elements are
configurable in BESTCOMSPlus under
Programmable Outputs, Configurable
Elements. The user can assign a string of up
to 16 characters and configure whether the
element should generate an alarm or provide
status only. If used for alarm, the user's text is
what will appear in the event log.
Cross Current
Compensation
Disable
When true, this element disables cross current
compensation.
Custom LED
When true, this element sets the Custom
Alarm on the front panel.