19-12 9492600990
BESTlogicâ„¢Plus DECS-150
Name
Description
Symbol
Datalog Logic Status
1-6
When true, Logic Status x can be selected
and displayed in the data log and real-time
monitor.
Datalog Trigger
When true, this element triggers the datalog to
begin recording data.
Droop Disable
When true, this element disables droop when
the unit is operating in AVR mode.
External Tracking
Disable
When true, this element disables external
tracking.
Freeze APC Output
When true, the output of the APC PI controller
is frozen.
This can be used with the APC REMOTE
COMM FAIL status input to freeze APC output
when remote communication fails.
Freeze LVRT Output
When true, the output of the LVRT controller
is frozen.
This can be used with the LVRT REMOTE
COMM FAIL status input to freeze LVRT
output when remote communication fails.
Grid Code Disable
When true, overall Grid Code functionality is
disabled.
Internal Tracking
Disable
When true, this element disables internal
tracking.
LFSM Disable
When true, Grid Code LFSM is disabled