19-16 9492600990
BESTlogicâ„¢Plus DECS-150
Name
Description
Symbol
SCL Select
Secondary Settings
When true, this element selects the secondary
settings for SCL.
Soft Start Select
Secondary Settings
When true, this element selects the secondary
settings for softstart.
Start Enable
When true, this element starts the unit.
Stop Enable
When true, this element stops the unit.
UEL Disabled in
Manual Mode
When true, this element disables UEL when
the unit is operating in Manual mode.
UEL Select
Secondary Settings
When true, this element selects secondary
settings for UEL.
Underfrequency V/HZ
Disable
When true, this element disables the V/Hz
Underfrequency limiter.
User Programmable
Alarm 1-16
When true, this element triggers a
programmable alarm.
Var/PF Mode
The var input selects var control and the PF
input selects power factor control.
Var/PF Selection
Enable
When true, this element allows the selection
of var and PF.
Voltage Matching
Disable
When true, this element disables voltage
matching when the unit is operating in AVR
mode.