25-16 9492600990
Modbus
®
Communication DECS-150
Group
Name
Register
Type
Bytes
R/W
Range
Grid Code Parameters
APC Enable
914 bit 8
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Disconnect Timing
914 bit 9
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Disconnect Timed Out
914 bit 10
Uint16
2
R
True=1 False=0
Grid Code Parameters
LVRT Remote Communications Active
914 bit 11
Uint16
2
R
True=1 False=0
Grid Code Parameters
APC Active
914 bit 12
Uint16
2
R
True=1 False=0
Grid Code Parameters
LVRT Remote Communications Fail
914 bit 13
Uint16
2
R
True=1 False=0
Grid Code Parameters
APC Remote Communications Fail
914 bit 14
Uint16
2
R
True=1 False=0
Grid Code Parameters
APC Output Limit
914 bit 15
Uint16
2
R
True=1 False=0
Grid Code Parameters
LFSM Recovery Active
915 bit 0
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Disabled
915 bit 1
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Continuous Operation
915 bit 2
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Frequency Low Timing
915 bit 3
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Frequency High Timing
915 bit 4
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Volts Low Timing
915 bit 5
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Volts High Timing
915 bit 6
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Out of Range Timing
915 bit 7
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Disconnected
915 bit 8
Uint16
2
R
True=1 False=0
Grid Code Parameters
GCC Reconnect Timing
915 bit 9
Uint16
2
R
True=1 False=0
Grid Code Parameters
LFSM Over Active
915 bit 10
Uint16
2
R
True=1 False=0
Grid Code Parameters
LFSM Under Active
915 bit 11
Uint16
2
R
True=1 False=0
Grid Code Parameters
LFSM Normal Operation
915 bit 12
Uint16
2
R
True=1 False=0
Grid Code Parameters
LVRT Modbus Communications Fail
915 bit 13
Uint16
2
R
True=1 False=0
Reserved
915 bit 14
Reserved
915 bit 15
Grid Code Parameters
APC Modbus Communications Fail
916 bit 0
Uint16
2
R
True=1 False=0
Reserved
916 bit 1
Reserved
916 bit 2
Grid Code Parameters
APC Remote Communications Active
916 bit 3
Uint16
2
R
True=1 False=0
Grid Code Parameters
Freeze LVRT Output from PLC
916 bit 4
Uint16
2
R
True=1 False=0
Grid Code Parameters
Freeze APC Output from PLC
916 bit 5
Uint16
2
R
True=1 False=0
Grid Code Parameters
APC Bridge Active
916 bit 6
Uint16
2
R
True=1 False=0
Grid Code Parameters
LVRT Bridge Active
916 bit 7
Uint16
2
R
True=1 False=0
Alarms
External Tracking Communications Loss
916 bit 8
Uint16
2
R
True=1 False=0
Metering
Table 25-7. Metering Group Parameters
Group
Name
Register
Type
Bytes
R/W
Unit
Range
Per Unit Meter
Vab
1000
Float
4
R
Per Unit
-10 10
Per Unit Meter
Vbc
1002
Float
4
R
Per Unit
-10 10
Per Unit Meter
Vca
1004
Float
4
R
Per Unit
-10 10
Per Unit Meter
V Average
1006
Float
4
R
Per Unit
-10 10
Per Unit Meter
Ia
1008
Float
4
R
Per Unit
-10 10
Per Unit Meter
Ib
1010
Float
4
R
Per Unit
-10 10
Per Unit Meter
Ic
1012
Float
4
R
Per Unit
-10 10
Per Unit Meter
I Average
1014
Float
4
R
Per Unit
-10 10
Per Unit Meter
kW
1016
Float
4
R
Per Unit
-10 10
Per Unit Meter
kVA
1018
Float
4
R
Per Unit
-10 10
Per Unit Meter
Kvar
1020
Float
4
R
Per Unit
-10 10
Per Unit Meter
Positive Sequence Voltage
1022
Float
4
R
Per Unit
-10 10
Per Unit Meter
Negative Sequence Voltage
1024
Float
4
R
Per Unit
-10 10
Per Unit Meter
Positive Sequence Current
1026
Float
4
R
Per Unit
-10 10