9492600990 25-21
DECS-150 Modbus
®
Communication
Name
Register
Type
Bytes
R/W
Unit
Range
UEL Primary Curve X3
1764
Float
4
R W
kilowatt
0–62
UEL Primary Curve X4
1766
Float
4
R W
kilowatt
0–62
UEL Primary Curve X5
1768
Float
4
R W
kilowatt
0–62
UEL Primary Curve Y1
1770
Float
4
R W
kilovar
0–62
UEL Primary Curve Y2
1772
Float
4
R W
kilovar
0–62
UEL Primary Curve Y3
1774
Float
4
R W
kilovar
0–62
UEL Primary Curve Y4
1776
Float
4
R W
kilovar
0–62
UEL Primary Curve Y5
1778
Float
4
R W
kilovar
0–62
UEL Primary Power Filter TC
1780
Float
4
R W
Second
0–20
UEL Primary Voltage Dependent Exponent
1782
Float
4
R W
n/a
0–2
UEL Secondary Curve X1
1784
Float
4
R W
kilowatt
0–62
UEL Secondary Curve X2
1786
Float
4
R W
kilowatt
0–62
UEL Secondary Curve X3
1788
Float
4
R W
kilowatt
0–62
UEL Secondary Curve X4
1790
Float
4
R W
kilowatt
0–62
UEL Secondary Curve X5
1792
Float
4
R W
kilowatt
0–62
UEL Secondary Curve Y1
1794
Float
4
R W
kilovar
0–62
UEL Secondary Curve Y2
1796
Float
4
R W
kilovar
0–62
UEL Secondary Curve Y3
1798
Float
4
R W
kilovar
0–62
UEL Secondary Curve Y4
1800
Float
4
R W
kilovar
0–62
UEL Secondary Curve Y5
1802
Float
4
R W
kilovar
0–62
SCL Primary Reference Hi
1804
Float
4
R W
Amp
0–66000
SCL Primary Reference Lo
1806
Float
4
R W
Amp
0–66000
SCL Primary Time Hi
1808
Float
4
R W
Second
0–60
SCL Primary No Response Time
1810
Float
4
R W
Second
0–10
SCL Secondary Reference Hi
1812
Float
4
R W
Amp
0–66000
SCL Secondary Reference Lo
1814
Float
4
R W
Amp
0–66000
SCL Secondary Time Hi
1816
Float
4
R W
Second
0–60
SCL Secondary No Response Time
1818
Float
4
R W
Second
0–10
OEL Primary Takeover Reset Time
Coefficient Off
1820
Float
4
R W
n/a
0.01100
OEL Primary Takeover Reset Time
Coefficient On
1822
Float
4
R W
n/a
0.01100
OEL Secondary Takeover Reset Time
Coefficient Off
1824
Float
4
R W
n/a
0.01100
OEL Secondary Takeover Reset Time
Coefficient On
1826
Float
4
R W
n/a
0.01100
OEL Primary Takeover Reset Type Off
1828
Uint32
4
R W
n/a
Inverse=0
Integrating=1
Instantaneous=2
OEL Primary Takeover Reset Type On
1830
Uint32
4
R W
n/a
Inverse=0
Integrating=1
Instantaneous=2
OEL Secondary Takeover Reset Type Off
1832
Uint32
4
R W
n/a
Inverse=0
Integrating=1
Instantaneous=2
OEL Secondary Takeover Reset Type On
1834
Uint32
4
R W
n/a
Inverse=0
Integrating=1
Instantaneous=2
Setpoints
Table 25-9. Setpoint Group Parameters
Name
Register
Type
Bytes
R/W
Unit
Range
Field Current Regulation Setpoint
2200
Float
4
R W
Amp
Setpoint adjustment range determined
by registers 2212 and 2214.
Field Current Regulation Traverse Rate
2202
Float
4
R W
Second
1–200