9492600990 25-25
DECS-150 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
System Configuration
Operating Mode
2510
Int32
4
R W
n/a
Generator=0
Motor=1
Configuration Settings
Table 25-11. Configuration Settings Group Parameters
Group
Name
Register
Type
Bytes
R/W
Unit
Range
System
Configuration
Nominal Frequency
2600
Uint32
4
R W
n/a
50 Hz=50 60 Hz=60
System
Configuration
Metric English
2602
Uint32
4
R W
n/a
English=0 Metric=1
System
Configuration
DECS Auxiliary Summing Mode
2604
Uint32
4
R W
n/a
Voltage=0 Var=1
System
Configuration
DECS Auxiliary Input Mode
2606
Uint32
4
R W
n/a
Voltage=0 Current=1
System
Configuration
DECS Auxiliary Input Function
2608
Uint32
4
R W
n/a
DECS Input=0
PSS Test Input=1
Grid Code Input=3
System
Configuration
DECS Auxiliary Voltage Gain
2610
Float
4
R W
n/a
-99 99
System
Configuration
DECS Auxiliary Current Gain
2612
Float
4
R W
Percent
-30 30
System
Configuration
DECS Auxiliary FCR Gain
2614
Float
4
R W
n/a
-99 99
System
Configuration
DECS Auxiliary var Gain
2616
Float
4
R W
n/a
-99 99
System
Configuration
DECS Auxiliary PF Gain
2618
Float
4
R W
n/a
-99 99
System
Configuration
DECS Auto Track Time Delay
2620
Float
4
R W
Second
0–8
System
Configuration
DECS Auto Track Traverse Rate
2622
Float
4
R W
Second
1–80
System
Configuration
DECS Null Balance Level
2624
Float
4
R W
Percent
0–9999
System
Configuration
DECS Auto Trans Time Delay
2626
Float
4
R W
Second
0–8
System
Configuration
DECS Auto Trans Traverse Rate
2628
Float
4
R W
Second
1–80
System
Configuration
DECS Power Input Base Voltage
2630
Float
4
R W
Volt
1–277
System
Configuration
Ambient Temperature
2632
Uint32
4
R W
n/a
Ambient 70°C=0
Ambient 55°C=1
Gen Volt
Configuration
Connection
2634
Int32
4
R W
n/a
PT_CA=2 PT_3W_D=7
Gen Volt
Configuration
Ratio Primary
2636
Float
4
R W
n/a
1–500000
Gen Volt
Configuration
Ratio Secondary
2638
Float
4
R W
n/a
1–600
Gen Volt
Configuration
Rated Primary LL
2640
Float
4
R W
Volt
1–90000
Bus Volt
Configuration
Connection
2642
Int32
4
R W
n/a
PT_CA=2 PT_3W_D=7
Bus Volt
Configuration
Ratio Primary
2644
Float
4
R W
n/a
1–500000
Bus Volt
Configuration
Ratio Secondary
2646
Float
4
R W
n/a
1–600
Bus Volt
Configuration
Rated Primary LL
2648
Float
4
R W
Volt
1–90000
Gen Current
Configuration
Connection
2650
Int32
4
R W
n/a
CT_B=1 CT_ABC=6
Gen Current
Configuration
Ratio Primary
2652
Float
4
R W
n/a
1–99999