9492600990 25-29
DECS-150 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
Configurable Protection 1
Parameter
Selection
3226
Int32
4
R W
n/a
Gen VAB=0 Gen VBC=1 Gen
VCA=2 Gen V Average=3 Bus
Freq=4 Bus VAB=5 Bus VBC=6
Bus VCA=7 Gen Freq=8 Gen PF=9
KWH=10 KVARH=11 Gen IA=12
Gen IB=13 Gen IC=14 Gen I
Average=15 KW Total=16 KVA
Total=17 KVAR Total=18 EDM
Ripple=19 Vfd=20 Ifd=21 Auxilary
Input Voltage=22 Auxilary Input
Current (mA)=23 Setpoint
Position=24 Tracking_Error=25
Neg_Seq_V=26 Neg_Seq_I=27
Pos_Seq_V=28 Pos_Seq_I=29
PSS_Output=30 Power Input=49
KW A=50 KW B=51 KW C=52
KVAR A=53 KVAR B=54 KVAR
C=55 KVA A=56 KVA B=57 KVA
C=58 Gen VAN=59 Gen VBN=60
Gen VCN=61 Cross Current=62
GenScaledPF=63 Network Load
Share Error Percent=65 No Param
Selected=64 LVRT Output=66 APC
Output=67
Configurable Protection 1
Hysteresis
3228
Float
4
R W
Percent
0–100
Configurable Protection 1
Arming Delay
3230
Float
4
R W
Second
0–300
Configurable Protection 1
Stop Mode Inhibit
3232
Int32
4
R W
n/a
No=0 Yes=1
Configurable Protection 1
Threshold 1 Type
3234
Int32
4
R W
n/a
Disabled=0 Over=1 Under=2
Configurable Protection 1
Threshold 1 Pickup
3236
Float
4
R W
n/a
-999999 999999
Configurable Protection 1
Threshold 1
Activation Delay
3238
Float
4
R W
Second
0–300
Configurable Protection 1
Threshold 2 Type
3240
Int32
4
R W
n/a
Disabled=0 Over=1 Under=2
Configurable Protection 1
Threshold 2 Pickup
3242
Float
4
R W
n/a
-999999 999999
Configurable Protection 1
Threshold 2
Activation Delay
3244
Float
4
R W
Second
0–300
Configurable Protection 1
Threshold 3 Type
3246
Int32
4
R W
n/a
Disabled=0 Over=1 Under=2
Configurable Protection 1
Threshold 3 Pickup
3248
Float
4
R W
n/a
-999999 999999
Configurable Protection 1
Threshold 3
Activation Delay
3250
Float
4
R W
Second
0–300
Configurable Protection 1
Threshold 4 Type
3252
Int32
4
R W
n/a
Disabled=0 Over=1 Under=2
Configurable Protection 1
Threshold 4 Pickup
3254
Float
4
R W
n/a
-999999 999999
Configurable Protection 1
Threshold 4
Activation Delay
3256
Float
4
R W
Second
0–300
Configurable Protection 1
Label
3258
String
16
R W
n/a
0–16
Configurable Protection 2
Parameter
Selection
3266
Int32
4
R W
n/a
Gen VAB=0 Gen VBC=1 Gen
VCA=2 Gen V Average=3 Bus
Freq=4 Bus VAB=5 Bus VBC=6
Bus VCA=7 Gen Freq=8 Gen PF=9
KWH=10 KVARH=11 Gen IA=12
Gen IB=13 Gen IC=14 Gen I
Average=15 KW Total=16 KVA
Total=17 KVAR Total=18 EDM
Ripple=19 Vfd=20 Ifd=21 Auxilary
Input Voltage=22 Auxilary Input
Current (mA)=23 Setpoint
Position=24 Tracking_Error=25
Neg_Seq_V=26 Neg_Seq_I=27
Pos_Seq_V=28 Pos_Seq_I=29
PSS_Output=30 Power Input=49
KW A=50 KW B=51 KW C=52
KVAR A=53 KVAR B=54 KVAR
C=55 KVA A=56 KVA B=57 KVA
C=58 Gen VAN=59 Gen VBN=60
Gen VCN=61 Cross Current=62
GenScaledPF=63 Network Load
Share Error Percent=65 No Param
Selected=64 LVRT Output=66 APC
Output=67
Configurable Protection 2
Hysteresis
3268
Float
4
R W
Percent
0–100
Configurable Protection 2
Arming Delay
3270
Float
4
R W
Second
0–300