25-40 9492600990
Modbus
®
Communication DECS-150
Name
Register
Type
Bytes
R/W
Unit
Range
Min Frequency Reconnect
4956
Float
4
R W
Hertz
4070
Max Frequency Reconnect
4958
Float
4
R W
Hertz
4070
Min V Bus Reconnect
4960
Float
4
R W
Per Unit
0.1–1
Max V Bus Reconnect
4962
Float
4
R W
Per Unit
1–1.3
Recovery Time LFSM
4964
Float
4
R W
Minute
0.1–90
Recovery Power Increase Rate Percent
4966
Float
4
R W
Percent Per
Second
0.00110
Recovery Power Decrease Rate Percent
4968
Float
4
R W
Percent Per
Second
0.00110
Reserved
4970-74
Active Power Level 1
4976
Float
4
R W
Per Unit
-2 – 2
Active Power Level 2
4978
Float
4
R W
Per Unit
-2 – 2
Active Power Level 3
4980
Float
4
R W
Per Unit
-2 – 2
Active Power Level 4
4982
Float
4
R W
Per Unit
-2 – 2
LFSM U Max Power Limit Start
Frequency
4984
Float
4
R W
Hertz
4070
LFSM O Max Power Limit Start
Frequency
4986
Float
4
R W
Hertz
4070
LFSM Power Increase Rate Percent
4988
Float
4
R W
Percent Per
Second
0.3310
LFSM Power Decrease Rate Percent
4990
Float
4
R W
Percent Per
Second
0.3310
APC Gain
4992
Float
4
R W
n/a
-100 100
Q Volt Limit Adjust Source
4994
Uint32
4
R W
n/a
None=0
Auxiliary Input=1
Modbus=2
Q U Adjust Source
4996
Uint32
4
R W
n/a
None=0
Auxiliary Input=1
Modbus=2
PF Adjust Source
4998
Uint32
4
R W
n/a
None=0
Auxiliary Input=1
Modbus=2
Q Third Party Adjust Source
5000
Uint32
4
R W
n/a
None=0
Auxiliary Input=1
Modbus=2
Active Power Adjust Source
5002
Uint32
4
R W
n/a
None=0
Auxiliary Input=1
Modbus=2
Reserved
5004
Q Volt Limit Adjust Modbus
5006
Float
4
R W
Per Unit
-0.45 0.45
Q U Volt Bus for Zero Q Adjust Modbus
5008
Float
4
R W
n/a
-0.5 0.5
PF Reference Adjust Modbus
5010
Float
4
R W
Power Factor
-1 – 1
Q Third Party Adjust Modbus
5012
Float
4
R W
Per Unit
-0.45 0.45
Active Power Adjust Modbus
5014
Float
4
R W
Per Unit
-2 – 2
APC Bridge Enable
5016
Uint32
4
R W
n/a
Disabled=0
Enabled=1
LVRT Bridge Enable
5018
Float
4
R W
n/a
Disabled=0
Enabled=1
PF Active Power Level
5020
Float
4
R W
Per Unit
0–1