Parameter
52 V-Controller (BUS 6 VC)
5.03047.01 Baumüller Nürnberg Electronic GmbH & Co. KG
P122 M set operation mode
P123 M actual operation mode
This parameter displays the active operation mode.
P124 M error code
In case of a fault, the corresponding error code can be found here. This error is acknowledged
if the bit „reset fault“ in the control word (P120) is set from 0 to 1 or the input „error reset“ is
enabled (see P136 M mode).
If several errors are present, the next error is displayed immediately after acknowledgement.
Error codes see chapter maintenance, error messages.
P125 M error index
This parameter indicates the number of errors which are present. On acknowledgement of
each error the displayed value is decreased. The parameter contains the number 0 after ack
-
nowledging all errors.
P136 M mode
This parameter chooses the different options to acknowledge an error message (see V-cont-
troller terminal diagram). The error acknoledgement can be done via digital input 3 X26:17
DELETE ERROR.
P137 M state 1
Operation
mode
Mode Comment
-3 Uzk controller not changeable
Bit no. Meaning
0 0: errors are acknowledged individually with bit no. 7 0 → 1
1: errors are acknowledged in one go with bit no. 7 0 → 1
1 ... 15 reserved
Bit no. Meaning
0 ... 3 Shows the state number displayed in the 7 segment display
4, 5 00: drive displays no error
01: error has occurred, error reaction is set in P189
6 ... 15 reserved