7.11 Ramp Function Generator
Function:
The ramp function generator (RFG) manages the 4 set value inputs, which can alternatively be switched
to the output. The ramp-up and ramp-down times can be set separately for each input.
(If set to STOP by means of P013, only the ramp-down time can be adjusted)
All inputs and the output of the ramp function generator are relative parameters (± 100 %) and standard-
ized to maximum speed (P019).
The ramp steepness for the acceleration and braking procedures are determined by the ramp-up and
ramp-down times. The times thus refer to 100 % set value alteration.
NOTE
If the inputs are used für intermediate circuit voltage 100 % ↔ 1000 V.