Parameter
68 V-Controller (BUS 6 VC)
5.03047.01 Baumüller Nürnberg Electronic GmbH & Co. KG
Parameter overview:
Parameter description
P014 RFG state
Displays the function module´s state.
Parameter Name Range
min. ... max.
Unit Display
only
P014 RFG state 0000 ... FFFF
!
P013 RFG mode 0000 ... 007F
P002 RFG input 1 -100,00 ... 100,00 %
P004 RFG input 2 -100,00 ... 100,00 %
P006 RFG input 3 -100,00 ... 100,00 %
P003 RFG ramp-up time 1 0,00 ... 650,00 s
P010 RFG ramp-down time 1 0,00 ... 650,00 s
P005 RFG ramp-up time 2 0,00 ... 650,00 s
P011 RFG ramp-down time 2 0,00 ... 650,00 s
P007 RFG ramp-up time 3 0,00 ... 650,00 s
P012 RFG ramp-down time 3 0,00 ... 650,00 s
P016 RFG rounding 0 ... 60000 ms
P001 RFG output -100,00 ... 100,00 %
!
Bit no. Meaning
0 ... 2 000: STOP 001: RUN
3 1: error in function module, error code see M error code (P124)
4 1: RFG output is set internally to 0 (RFG_LOCKED)
5 1: RFG was stopped on the ramp (RFG_STOP)
6 1: RFG input is set internally to set value 0 (RFG_ZERO)
7 reserved
8 1: ramp-up procedure is active
9 1: ramp-down procedure is active
10 ... 11 reserved
12 1: RFG output = RFG input (set value reached)
13 ... 15 reserved