Parameter
V-Controller (BUS 6 VC) 69
Baumüller Nürnberg Electronic GmbH & Co. KG 5.03047.01
P013 RFG mode
The input selection chooses one out of four inputs of the ramp function generator and acti-
vates the set value limitation.
P002 RFG input 1
P004 RFG input 2
P006 RFG input 3
All 3 inputs are balanced and can be written via the serial interface, position controller and
the set value generator as well as the analog set value input.
P003 RFG ramp-up time 1
P005 RFG ramp-up time 2
P007 RFG ramp-up time 3
The acceleration assigned to the inputs can be set via the ramp-up times. The time selected
here correspond to a set value alteration of 100 %.
P010 RFG ramp-down time 1
P011 RFG ramp-down time 2
P012 RFG ramp-down time 3
The deceleration assigned to the inputs can be set via the ramp-down times. The time selec-
ted here correspond to a set value alteration of 100 %.
P016 RFG rounding
A first-order time delay element is implemented in order to round off ramp corners. The time
constants of the PT
1
device can be set by this parameter.
Bit no. Meaning
0 ... 2 000: reserved
001: input 1
010: input 2
011: input 3
100: sum of input 1 and input 2
3 1: negative set values are disabled
4 1: positive set values are disabled
5 1: change polarity of actual set value
6 ... 15 reserved
NOTE
The value of P002 (RFG input) is changed automatically, when writing on P087 (PS Uzk nominal).