Parameter
60 V-Controller (BUS 6 VC)
5.03047.01 Baumüller Nürnberg Electronic GmbH & Co. KG
! Source load of the parameters
If a source load is carried out the standard values of the parameter list are set and therefore a defined
state is reached.
The procedure of the source load is mentioned below:
1. P190 = 0 command reset data set management
2. P190 = 7 command delete data set
3. Wait until P191 = 0003
4. Switch off power supply of controller
5. Switch on power supply of controller
6. Now is displayed: P191 = 000B stand-by with error
P192 = 0002 data set not available
P124 = 0902
The controller´s state is fault
7. P190 = 0 command reset data set management
8. P190 = 5 command store data set
9. Wait until P191 = 000B
! Store the write protected data set
1. P190 = 0 command reset data set management
2. P190 = 8 command input password
3. P190 = password 1
4. P190 = 0 command reset data set management
5. P193 = 3 DS no. write-protected data set
6. P190 = 5 command store data set
! Change article no. of data set
1. P190 = 0 command reset data set management
2. P190 = 8 command input password
3. P190 = password 2
4. P190 = 0 command reset data set management
5. P193 = 0, 1, 2, (3)* data set no.
6. P194 = new article no. hexadecimal number
7. P190 = 5 command store data set
* only possible, if password 1 was already given