Parameter
72 V-Controller (BUS 6 VC)
5.03047.01 Baumüller Nürnberg Electronic GmbH & Co. KG
Parameter description
P150 SVG state
This parameter displays the internal function module state.
P140 SVG target Pxxx
To this parameter no. the output value is written (e.g. parameter P002, input 1 ramp function
generator).
P141 SVG output value
The actual set value is displayed here.
P142 SVG set value 1
P143 SVG set value 2
P144 SVG set value 3
P145 SVG set value 4
Parameter values between -100 % and +100 % can be assigned to these 4-amplitude-param-
eters. The amplitudes are connected to the output value according to the time assigned to
them.
P146 SVG time 1
P147 SVG time 2
P148 SVG time 3
P149 SVG time 4
Values between 8 ms and 60 s can be assigned to these time parameters. The corresponding
amplitudes are switched to the output value during these time intervals.
Bit no. Meaning
0 ... 2 000: STOP 001: RUN
3 ... 15 reserved