Parameter
V-Controller (BUS 6 VC) 89
Baumüller Nürnberg Electronic GmbH & Co. KG 5.03047.01
Error table
Parameter overview
Parameter description
P170 SI state
Write-access to the drive parameters is managed via parameter M communication source
(P126) in the drive manager. The drive parameter can only be altered via the service interface
when bit no. 0 of this parameter is set to 1. If the bit is set to 0 write-access is inhibited and
only read-access to the parameter values granted.
See also M communication source (P126)
P171 SI baud rate
The service baud rate can only be displayed and is set to a fixed value of 9600 baud.
Error number Meaning
0 No fault
1 Element is not available
2 Datum is too short
3 Datum is too long
4 Datum is not alterable
5 Parameter is write protected
6 Datum is smaller than minimum value
7 Datum is greater than maximum value
8 Datum is invalid
9 Obtaining of parameter is invalid
Parameter Name Range
min. ... max.
Unit Display
only
P170 SI state 0000 ... FFFF
!
P171 SI baud rate 50 ... 19200 Baud
!
P172 SI mode 0000 ... 0003
Bit no. Meaning
0 ... 3 status of function module
0001: RUN (all parameters can be read and write)
0000: STOP (all parameters can be read only)
11 ... 15 reserved