Parameter number Parameter Description Unit Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
750 1050 1350 Room influence Influence of the room temperature and the
outside temperature on calculating the flow
temperature: ---%: Simple regulation in ac
cordance with outside weather conditions:
1…99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
% 50
760 1060 1360 Room temp
limitation
Cuts the circulating pump if the room tempera
ture exceeds the current set point + parameter
760, 1060, 1360.
°C 0.5
809 1109 1409 Continuous pump
operation
No : The heating circuit / boiler pump may be
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de
cline in temperature and when the room tem
perature set point is reached.
– no
834 1134 1434 Actuator running
time
Setting the stroke of the servomotor on the
mixing valve used
seconds 30
850 1150 1450 Floor curing
function
Controlled screed-drying function:
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at 25 °C and 4 days at 55 °C.
Curing heating : Active for 18 days, 6 days
from 25 °C to 55 °C increasing by 5 °C a
day, 6 days at 55 °C, 6 days from 55 °C to
25 °C diminishing by 5 °C a day.
Functional/curing heating : "Functional Heat
ing" cycle first, and then "Ready for Occupa
tion".
Manually : Regulation is based on the "Man
ual Control Drying" set point.
S Off
851 1151 1451 Floor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C 25
855 1155 1455 Floor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘---‘ the function is
deactivated.
- ‘---’
856 1156 1456 Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘---‘ the function is deactivated.
- ‘---’
Tab.49 Temps / mode hot water menu
Parameter
number
Parameter Description Factory setting
1600 Operating mode Off: Permanent running at the frost protection set point.
On : Domestic hot water loading is done automatically at the
comfort set point.
Eco : The temperature maintenance function is deactivated.
On
1610 Hot water temp
setpoint
DHW set point during release times 60°C
1612 Reduced temp
setpoint
Reduced temperature set point outside release times 35°C
10 Settings