Parameter number Parameter Description Unit Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
750 1050 1350 Room influence Influence of the room temperature and the
outside temperature on calculating the flow
temperature: ---%: Simple regulation in ac
cordance with outside weather conditions:
1…99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
% 50
760 1060 1360 Room temp
limitation
Cuts the circulating pump if the room tempera
ture exceeds the current set point + parameter
760, 1060, 1360.
°C 0.5
809 1109 1409 Continuous pump
operation
No : The heating circuit / boiler pump may be
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de
cline in temperature and when the room tem
perature set point is reached.
no
834 1134 1434 Actuator running
time
Setting the stroke of the servomotor on the
mixing valve used
seconds 30
850 1150 1450 Floor curing
function
Controlled screed-drying function:
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at 25 °C and 4 days at 55 °C.
Curing heating : Active for 18 days, 6 days
from 25 °C to 55 °C increasing by 5 °C a
day, 6 days at 55 °C, 6 days from 55 °C to
25 °C diminishing by 5 °C a day.
Functional/curing heating : "Functional Heat
ing" cycle first, and then "Ready for Occupa
tion".
Manually : Regulation is based on the "Man
ual Control Drying" set point.
S Off
851 1151 1451 Floor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C 25
855 1155 1455 Floor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘---‘ the function is
deactivated.
- ‘---’
856 1156 1456 Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘---‘ the function is deactivated.
- ‘---’
Tab.49 Temps / mode hot water menu
Parameter
number
Parameter Description Factory setting
1600 Operating mode Off: Permanent running at the frost protection set point.
On : Domestic hot water loading is done automatically at the
comfort set point.
Eco : The temperature maintenance function is deactivated.
On
1610 Hot water temp
setpoint
DHW set point during release times 60°C
1612 Reduced temp
setpoint
Reduced temperature set point outside release times 35°C
10 Settings
82 POWER HT + 7702630 - v02 - 11082018

Table of Contents

Other manuals for Baxi POWER HT+ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi POWER HT+ Series and is the answer not in the manual?

Baxi POWER HT+ Series Specifications

General IconGeneral
ModelPOWER HT+ Series
CategoryBoiler
Installation TypeWall-mounted
Heat Exchanger MaterialStainless Steel
Warranty2 years
Fuel TypeNatural Gas
Control SystemIntegrated Control
Ignition TypeElectronic

Related product manuals