X2 Control communication with BFI-E3 by Modbus TCP
SER0020_V1.0.0 2020-11
26 (31)
Parameters
Parameter Registers and Scaling
All user adjustable parameters within the drive are accessible by Modbus and can be Read or Written to. For
further information regarding the parameter functions and specific settings, please refer to the User Guide.
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
0: Ramp to stop + Main Loss Ride Through
1: Coast to stop
2: Ramp to stop + Fast Stop
3 : AC Flux Braking + Fast Stop
Maximum value equals to the sync speed of
a typical 2-pole motor
0: Terminal Control
1: Keypad forward only
2: Keypad forward and reverse
3: Modbus control mode
4: Modbus control with ramp control
5 : PID control
6 : PID control with analog speed sum
7 : CAN Open
8 : CAN Open + Ramp Control
9 : Slave Mode
0 : Industrial Mode
1 : Pump Mode
2 : Fan Mode
See user guide for function details
0: 0…10V 1: b 0…10V
2: 0…20mA 3: t 4…20mA
4: r 4…20mA 5: t 20…4mA
6: r 20…4mA 7 : 10…0V
Effective switching
frequency
0 = 4kHz 1 = 8kHz
2 = 12kHz 3 =16kHz
4 = 24kHz 5 = 32kHz
See user guide for function details
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)
Internal value (3000 = 50.0Hz)