X2 Control communication with BFI-E3 by Modbus TCP
SER0020_V1.0.0 2020-11
27 (31)
Normal.dotm
, 2020-07-01
Register
Para-
meter
Description
Format
Min
Max
Data format
153
25
Analog output
function
U16
0
10
See user guide for function details
154
26
Skip frequency
U16
0
P-01
Internal value (3000 = 50.0Hz)
155
27
Skip freq band
U16
0
P-01
Internal value (3000 = 50.0Hz)
156
28
V/F adjust voltage
U16
0
P-07
100 = 100V
157
29
V/F adjust frequency
U16
0
P-09
50 = 50Hz
158
30
Start mode select
U16
0
6
0: Edgr-r 1: Auto_0
2…6: Auto_1 to Auto_5
159
31
Keypad restart mode
U16
0
7
See user guide for details
160
32
DC injection enable
U16
See Below
161
33
Spin start enable
U16
0
2
See user guide for function details
162
34
Brake circuit enable
U16
0
4
See user guide for function details
163
35
Analog input scaling
U16
0
20000
1000 = 100%
164
36
Communication
Settings
WORD
See Below
165
37
Access code
definition
U16
0
9999
166
38
Parameter lock
U16
0
1
0: Unlock or 1: Locked
167
39
Analog input offset
U16
-5000
5000
1dp, e.g. 300=30.0%
168
40
Display scaling
factor
U16
See Below
169
41
User PI P gain
U16
1
300
1dp, e.g. 10 = 1.0
170
42
User PI I time
constant
U16
0
300
1dp, e.g. 10 = 1.0s
171
43
User PI mode select
U16
0
1
See user guide for more information
172
44
User PI reference
select
U16
0
1
See user guide for more information
173
45
User PI digital
reference
U16
0
1000
1dp, e.g. 100 =10.0%
174
46
User PI feedback
select
U16
0
3
See user guide for more information
175
47
2nd an input format
U16
0
6
0: 0...10V 1: 0…20mA
2: t 4...20mA 3: r 4...20mA
4: t 20...4mA 5: r 20...4mA
6: Ptc-th
176
48
Standby Mode Timer
U16
0
250
1dp, e.g. 250 = 25.0s
177
49
PI Wake Up Error
Level
U16
0
1000
1dp, e.g. 50 = 5.0%
178
50
User Relay Output
Hysteresis
U16
0
1000
1dp e.g. 100 = 10.0%
179
51
Motor Control Mode
U16
0
4
0 : IM Vector 1 : V/F
2 : PM Motor 3 : BLDC
Motor
4 : SynRM Motor 5 : LSPM
Motor
180
52
Motor Parameter
Autotune
U16
0
1
181
53
Vector Mode Gain
U16
0
2000
1dp, e.g. 500 = 50.0%
182
54
Maximum Current
Limit
U16
0
1750
1dp, e.g. 1000 = 100.0%
183
55
Motor Stator
Resistance
U16
0
65535
2dp, e.g. 100 = 1.00 ohm
184
56
Motor Stator d-axis
Inductance (Lsd)
U16
0
65535
1dp, e.g. 1000 = 100.0mH
185
57
Motor Stator q-axis
Inductance (Lsq)
U16
0
65535
1dp, e.g. 1000 = 100.0mH
186
58
DC Injection Speed
U16
0
P-01
3000 = 50.0Hz