6.6.2 Changing the measuring clamp
Two methods can be used to change the measuring clamp.
Changing with EDS195P switched off:
Disconnect clamp no longer required
Switch on EDS195P
Wait for "No CT connected" message
Set required clamp type
Connect related clamp
Wait for end of self-test.
Changing with the EDS195P in operation:
Disconnect clamp from the device
Wait for "No CT connected" message
Set required clamp type
Connect related clamp
Wait for end of self-test.
6.6.3 Improved legibility due to display lighting
Press the button at the bottom left to improve the legibility of text and symbols.
Switch off the lighting by pressing the button again.
6.6.4 Changing between insulation fault location I
ΔL
and
residual current measurement I
Δn
operating modes
Here you can select the measuring function. I
Δn
for residual current measurement preferably in
TN/TT systems. I
ΔL
for insulation fault location in IT systems.
Avoid changing the mode during insulation fault location.
6.6.5 Quickly checking the response values for I
ΔL
and I
Δn
Press the INFO button three times to display the actual response values.
6.6.6 Checking Info menu
The following information appears on the display in succession on pressing the INFO button:
Device name, time, date and manufacturer
Software version with date
Actual response values I
ΔL
and I
Δn
Status information, coded, see page 58