Operation
36
EDS309x_D00012_03_M_XXEN/11.2014
6.6.7 Significance of the display elements
The elements shown relate to the EDS mode (I
ΔL
). This mode is used for insulation fault location.
6.7 Standard displays on the EDS195P
6.7.1 EDS measurement (I
ΔL
)
6.7.1.1 Standard display if there is no cable to be measured in the clamp
The device is in the EDS mode (
I
ΔL
).
A measured locating current
I
ΔL
is not indicated, as there is no conductor in the measuring clamp.
The display shows the timer count (29…0).
1
Indication of the locating current pulse:
= Positive pulse,
= Pause or no measurement possible when permanently displayed
= Negative pulse
29
= Timer (29…0) shows the duration of a measurement of an outgoing
circuit
2
Indication of the selected transformer type:
- PSA30xx = PSA30… / PSA3165 (suitable for I
Lmax
= 50 mA)
- W/WR/WS = W…. / WR…. / WS…. (suitable for I
Lmax
= 50 mA)
- PSA33xx = PSA33… (suitable for I
Lmax
= 5 mA)
- W/WS-8000 = W….-8000 / WS….-8000 (suitable for I
Lmax
= 5 mA)
- WF = WF…. (only suitable for I
Δn
)
3
H = Hold function is activated; measured value indication "frozen"
4
M = Fault memory is activated
5
Loudspeaker symbol visible:
The presence of an alarm is also output audibly
6
Charge state of the rechargeable battery in the steps 0%, 33%, 66%,100%
7
Resp. = Response value IΔL
8
IΔL = Indication of the actual locating current measured
I L = 8mA
Resp. = 5mA
MH
PSA30xx
I
L
= mA
Anspr. = 5mA
M
PSA30xx
29