6.13 Coupling device AGE185 for higher system voltages
This option is available for the variants EDS3090PG, EDS3090PG-13 and EDS3096PG with the locat-
ing current injectors PGH185 and PGH186. The coupling device AGE185 expands the nominal volt-
age range of the insulation fault location system EDS309…
The AGE185 reduces the losses in the locating current injector PGH18… As a result it makes it possi-
ble to connect the PGH18… to nominal system voltages up to AC 790 V or DC 960 V.
Assembly, connection and placing in operation
Connection and placing in operation only by an electrical technician!
It is imperative the existing safety regulations are followed!
The ends of the wires from the AGE185 can be connected, as necessary and to suit the local situation,
to the system's PE terminal and the PE socket on the PGH186; it is not necessary to take into account
the polarity.
Connection diagram
Abb. 6.3: Connection diagram EDS309… with AGE185
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused.
For this reason avoid any contact whatsoever with active conductors on con-
necting the PGH or the AGE.