6.11 Menu structure
The menu structure is shown schematically in the following.
Level 1 Level 2 Level 3
or explanation
1. Exit
2. Settings
1. Exit
2. I
ΔL ALM: 0.2…10 mA
3. IΔn ALM: 10 mA…10 A
4. Memory: on/off
5. Buzzer: on/off
6. Frequ.: 50/60Hz/up to 1kHz
7. Harmonics: on/off
Response value measured locating current I
Δ
L
Response value residual current I
Δ
n
Audible alarm
Frequency of the system monitored
Indication of harmonics and total harmonic
distortion THD in %
3. System 1. Exit
2. Language
1. Exit
2. German
3. English
4. French
5. Russian
3. Clock 1. Exit
2. Format: D.M.Y
3. Date
4. Time
4. Contrast: 0…15
Contrast setting for display
4. Harmonics 1. Exit
2. H1 < 10 mA
3. H2 < 10 mA
.....
9. H8 < 10 mA
This menu item is used only for the indication
of harmonics from H1 to H8. To display the
harmonic with the greatest amplitude in the
standard display with the menu closed, the
menu item "7. Harmonics: on/off" on the Set-
tings menu is to be activated
5. IΔL alarms 1. Exit
2. Entries
Alarm No. 001
No. 002
No. ......
3. Delete 1. Exit
2. Delete Data
6. I
Δn logger 1. Exit
2. Entries
Entry No. 001
No. 002
No. ......
3. Change: 10…100 %
Percentage change from which logging
becomes active
4. Overwrite: yes/no
Overwrite oldest data record
5. Delete 1. Exit
2. Delete Data
7. Service
For service only