7.1 Technical specifications for the system EDS309…
The technical specifications stated in this section apply to the
components PGH18…, EDS195P, AGE185.
Environment/EMC
EMC................................................................................................................................................................................................................ IEC 61326-2-4
Operating temperature ................................................................................................................................................................................ -10…+ 55 °C
Climatic classes acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .................................................................................................................................3K5 (without condensation or icing)
Transport (IEC 60721-3-2) .........................................................................................................................................2K3 (without condensation or icing)
Long-term storage (IEC 60721-3-1) .........................................................................................................................1K4 (without condensation or icing)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .....................................................................................................................................................................................3M4
Transport (IEC 60721-3-2) .............................................................................................................................................................................................2M2
Long-term storage (IEC 60721-3-1) .............................................................................................................................................................................1M3
Other
Operating mode .......................................................................................................................................................................................... Continuous duty
Position in normal use......................................................................................................................................................................................................Any
Weight EDS309… ................................................................................................................................................................................................ ≤ 7000 g
Weight EDS309… with PSA3165 ....................................................................................................................................................................... ≤ 8500 g
Weight EDS3092 ................................................................................................................
................................................................................... ≤ 9000 g
Dimensions, case W x H x D ................................................................................................................................................................ 430 x 340 x 155 mm
7.2 Technical specifications PGH18…
Insulation coordination according to IEC 60664-1/IEC 60664-3
Rated voltage .......................................................................................................................................................................................................... 500 V AC
Rated surge voltage / degree of pollution ................................................................................................................................................................. 4 kV/3
Nominal system voltage U
n
PGH183.........................................................................................................................................................AC 42…460 Hz 20…265 V, DC 20…308 V
PGH185................................................................................................................................................ 3AC/AC 42…460 Hz 20…575 V, DC 20…504 V
PGH186.................................................................................................................................................... 3AC/AC 42…460 Hz 0…575 V, DC 0…504 V
Supply voltage
Supply voltage U
S
................................................................................................................................................................................AC 50…60 Hz 230 V
Operating range of U
S
................................................................................................................................................................................ 0.85…1.15 x U
S
Supply voltage U
S
version -13 ................................................................................................................................................. AC 50…60 Hz 90…132 V
PGH 183, PGH 185:
Power consumption ................................................................................................................................................................................................. ≤ 3 VA
PGH 186:
Power consumption ................................................................................................................................................................................................. ≤ 6 VA

Table of Contents