Function
2.2.6 Factory settings FAC
There are two types of reset:
2.2.6.1 Factory settings without interface
After restoring the factory settings, all previously changed settings are reset to the state upon de-
livery. The settings for the Modbus interface are not reset.
2.2.6.2 Factory settings with interface
After restoring the factory settings, all previously changed settings including the settings for the
Modbus interface and the device address are reset to the state upon delivery.
2.2.7 Combined function button (T/R button)
Reset = pressing the T/R button > 1 s < 3 s
Test = pressing the T/R button > 3 s < 6 s
NFC = pressing the T/R button > 6 s < 10 s
Addr. = pressing the T/R button > 10 s < 15 s
2.2.8 Fault memory
The fault memory can be enabled or disabled. Stored alarms are reset by pressing the T/R button
> 1 s and < 3 s when the fault memory is enabled. The fault memory is factory-set to enabled.