RCM410R-x_D00403_01_M_XXEN/09.2020 27
LINETRAXX® RCM410R-1/-2
Displays, memory
Display ........................................ status LED incl. LED bar graph
Display range measured value .................................. 0…100 %
Fault memory alarm messages ............................... on/off (on)*
Cable lengths for measuring current trans-
formers
Single wire ≥ 0.75 mm² ................................................ 0…1 m
Single wire, twisted ≥ 0.75 mm² .................................. 0…10 m
Shielded cable ≥ 0.75 mm² ......................................... 0…40 m
RS-485 interface
Protocol ...................................................................Modbus RTU
Baud rate ............................... max 115.2 kbits/s (19.2 kbits/s)*
Parity ...................................................... even, no, odd (even)*
Stop bits ........................................................... 1/2/auto (auto)*
Cable length (at 9.6 kbits/s).........................................≤ 1200 m
Cable: twisted pair ............................ min. J-Y(St)Y 2 x 0.6 mm²
Required terminating resistor ............................. 120 Ω (0.25 W)
Device address
3)
..........................................1…247 (100+SN)*
Switching elements
Switching elements ..................................1 changeover contact
Operating principle ......... N/C or N/O operation (N/C operation)*
Electrical endurance, number of cycles ............................ 10000
Connection
Connection type ............................................................... push-in
Connection properties
rigid ............................................0.2…1.5 mm² (AWG 24…16)
flexible ....................................... 0.2…1.5 mm² (AWG 24…16)
with ferrule ..................................................... 0.25…0.75 mm²
with ferrule .....................................................1.0…1.5 mm² **
** Use crimping pliers similar to CRIMPFOX 6 / Weidmüller PZ6/
PZ6/5 only.
Contact data acc. to IEC 60947-5-1:
Utilisation category ......... AC 13 AC 14 DC-12 DC-12 DC-12
Rated operat. voltage .....230 V 230 V 24 V 110 V 220 V
Rated operat. current ........ 5 A 3 A 1 A 0.2 A 0.1 A
Minimum contact rating
2)
........................1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC ............................................................................. IEC 62020
Ambient temperatures
Operation ..............................................................-25…+55 °C
Transport ..............................................................-40…+85 °C
Storage ..................................................................-40…+70 °C
Classification of climatic conditions acc. to IEC 60721 (ex-
cept condensation and formation of ice)
Stationary use (IEC 60721-3-3) ............................................ 3K23
Transport (IEC 60721-3-2) ...................................................2K11
Long-term storage (IEC 60721-3-1) .................................... 1K22
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ..........................................3M11
Transport (IEC 60721-3-2) ................................................... 2M4
Long-term storage (IEC 60721-3-1) .................................. 1M12
Other
Operating mode ....................................... continuous operation
Mounting ........................................................................ vertical
Degree of protection, internal components (DIN EN 60529) IP30
Degree of protection, terminals (DIN EN 60529) ................... IP20
Enclosure material ................................................ polycarbonate
DIN rail mounting acc. to ........................................... IEC 60715
Flammability class ....................................................... UL94 V-0
Documentation number ................................................... D00403
Weight ............................................................................≤ 100 g
*
Factory setting
1)
Can only be configured via RS-485
2)
Refers to relays that have not been operated with high contact cur-
rents
3)
Factory setting: 100 + last two digits of serial number
4)
See chapter 2.2.5.1
5)
See chapter 3.2.2.2
7.1 Standards & certifications
Devices of the RCM410R series have been de-
veloped according to the following standards:
• IEC 62020
7.2 Ordering information
Supply voltage U
S
Type Art. No.
AC/DC DC
24 V RCM410R-1 B74602000
100…240 V 24 V RCM410R-2 B74603000