RCM410R-x_D00403_01_M_XXEN/09.2020 21
LINETRAXX® RCM410R-1/-2
5.2 Register table
Address
(dec)
Register name Data type Bytes Mode Value/Unit/Comment Factory
setting
Device information (0-3999)
0 Device name String UTF8 32 RO e.g.: RCM410R-1
RCM410R-2
N/A
16 Article number String UTF8 32 RO e.g.: B74602000 (RCM410R-1)
B74603000 (RCM410R-2)
N/A
32 Serial number String UTF8 32 RO 10 digits e.g.: 2002123456
N/A
48 Manufacturer String UTF8 96 RO Bender GmbH & Co. KG
N/A
100 Application D number Uint16 2 RO 642 = D642
N/A
101 Application version number Uint16 2 RO xxx = Vx.xx
N/A
102 Application build number Uint16 2 RO
N/A
103 Boot loader D number Uint16 2 RO 641 = D641
N/A
104 Bootloader version number Uint16 2 RO xxx = Vx.xx
N/A
105 Boot loader build number Uint16 2 RO
N/A
106 Device status Uint32 4 RO Bit 0 (LSB): NFC - 0 = disabled, 1 = enabled
Bit 1: Potentiometer I
Δn
- 0 != ext, 1 = ext
Bit 2: Potentiometer ton - 0 != ext, 1 = ext
Bit 3-31: 0 (reserved)
N/A
Measured values (1000…1999)
1000 Residual current measured
value
Float 4 RO 0...50 [A]
N/A
Alarm status (20002999)
2000 Alarm status Uint16 2 RO 0 = no alarm
1 = prewarning
2 = main alarm
N/A
Range (30003999)
3000 Measuring range status Uint16 2 RO
0 : " "
within measuring range
1 : "<" below measuring range (not used)
2: ">" measuring range exceeded
N/A
Test status (40004999)
4000 Test status Uint16 2 RO 0 = no active test
1 = test active via T/R button,
2 = test active via interface
N/A
CT status (50005999)
5000 CT status Uint16 2 RO 0 = OK
1 = short circuit
2 = interruption
N/A