18 RCM410R-x_D00403_01_M_XXEN/09.2020
Operation and settings on the device
4.1.5 Potentiometer response delay t
on
Setting of the delay time t
on
.
4.1.6 T/R BUTTON
The T/R button activates dierent operating modes depending on how long it is pressed.
Overview
i
The NFC mode is available to the Bender service only.
4.1.6.1 "Reset" function
The "Reset" function resets stored alarm states.
4.1.6.2 "Test" function
The "Test" function simulates a residual current of 1.5 x I
Δn
for a period of
5 seconds. During this period, the device has the following states:
• Display of the alarm value via the LEDs and the interface.
• The relays switches if the alarm assignment "Test" has been activat-
ed.
• The test status can be read out via the interface:
– 0 = no test
– 1 = internal test
– 2 = external test (interface)
• t
on
and t
off
are set to 0 s for the duration of the test
ON
Bender
RCM410R
T / R
ton(s)
Ext 10 4
2
1
0,8
0,6
0,40,20
I∆n(A)
Ext 30 10
5
1
0,5
0,3
0,1,03,01
25
%
50
75
%
100
2
AL
1
S2S1
**
A2A2
A1A1
11 14 12
BA-+
The residual operating current and the pre-
warning must be exceeded at least for the set
response delay t
on
to trigger the respective
alarm. The amount by which the response val-
ue is exceeded is not relevant.
The parameter can only be changed via the in-
terface in switch position "Ext".
The set response delay t
on
is added to the oper-
ating time t
ae
.
Mode Period Status LED
Reset 1 s to 3 s ashes yellow
Test 3 s to 6 s ashes red
NFC 6 s to 10 s ashes blue
Addr. 10 s to 15 s ashes green
ON
Bender
RCM410R
T / R
ton(s)
Ext 10 4
2
1
0,8
0,6
0,40,20
I∆n(A)
Ext 30 10
5
1
0,5
0,3
0,1,03,01
25
%
50
75
%
100
2
AL
1
S2S1
**
A2A2
A1A1
11 14 12
BA-+