22 RCM410R-x_D00403_01_M_XXEN/09.2020
Modbus settings
Address
(dec)
Register name Data type Bytes Mode Value/Unit/Comment Factory
setting
Modbus RTU parameters (3200032099)
32000 Device address Uint16 2 RW 1…247 Last 2 digits
of the serial
number +
100
32001 Baud rate Uint32 4 RW 9600, 19200, 38400, 57600, 115200 19200
32003 Parity Uint16 2 RW 1 = even
2 = odd
3 = none
1
32004 Stop bits Uint16 2 RW 1 = 1
2 = 2
3 = automatic
3
Parameters (3210032199)
32100 Alarm assignment test Uint16 2 RW 1 = enabled
2 = disabled
1
32101 Operating mode Uint16 2 RW 1 = N/O principle
2 = N/C principle
2
32102 Alarm assignment
prewarning
Uint16 2 RW 1 = enabled
2 = disabled
2
32103 Alarm assignment main
alarm
Uint16 2 RW 1 = enabled
2 = disabled
1
32104 Alarm assignment
CT connection fault
Uint16 2 RW 1 = enabled
2 = disabled
1
32105 Alarm assignment device
error
Uint16 2 RW 1 = enabled
2 = disabled
1
32106 Fault memory Uint16 2 RW 1 = enabled
2 = disabled
1
32107 Residual operating current Uint32 4 RW 10…30000 [mA], step size 1 mA 10 mA
32109 Prewarning threshold Uint16 2 RW 50…100 [%], step size 1 % 50%
32110 Hysteresis Uint16 2 RW 10…25 [%], step size 1 % 15%
32111 CT connection monitoring Uint16 2 RW 1 = enabled
2 = disabled
1
32112 Response delay Uint32 4 RW 0…10000 [ms], step size 1 ms 0
32114 Delay on release Uint32 4 RW 0…999000 [ms], step size 1 ms 0
32116 Start-up delay Uint32 4 RW 0…999000 [ms], step size 1 ms 0