RCM410R-x_D00403_01_M_XXEN/09.2020 23
LINETRAXX® RCM410R-1/-2
Address
(dec)
Register name Data type Bytes Mode Value/Unit/Comment Factory
setting
Device error codes (58000…58999)
58000 Number of device errors Uint16 2 RO Number of active device errors
N/A
58001
Internal device error
Uint16 2 RO
0 = no device error
> 0 = internal device error
N/A
58002 Uint16 2 RO
N/A
58003 Uint16 2 RO
N/A
58004 Uint16 2 RO
N/A
58005 Uint16 2 RO
N/A
58006 Uint16 2 RO
N/A
58007 Uint16 2 RO
N/A
Control commands (60000)
60000 Function selection Uint16 2 WO Function selection register to control the
function of the following registers. Only
specied values are permitted.
1 = Set Modbus address
2 = Find device
4 = Reset to factory settings /
Reset parameters
6 = Test
7 = Reset
N/A
Function 1: Set Modbus address
60000 Function selection Uint16 2 WO 1 → Selection of "Set Modbus address"
function
N/A
60001 Serial number Uint32 4 WO Serial number of the device to which the
new Modbus address is assigned. The
new Modbus address is only assigned to
the device with the corresponding serial
number.
N/A
60003 Modbus address Uint16 2 WO 0…247 → New Modbus address N/A
Function 2: Find device
60000 Function selection Uint16 2 WO 2 → Selection of the "Find device"
function
N/A
60001 Pattern value part 1 Uint16 2 WO 61918 → Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2 Uint16 2 WO 0 → Safety pattern must be written for
the function to be executed
N/A
60003 Period Uint16 2 WO 0…300 → Period in seconds during
which the device lights up. If the device re-
ceives the value 0, the function is stopped.
N/A